Transformer dielectric loss tester 10kv transformer capacitance tester

Transformer Dielectric Loss Tester 10KV Transformer Capacitance TesterIntroduction:GDGS Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester is used to measure dissipation factor (PF) in heavy interference site such as power plants 

Featured Products

Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester

Transformer Dielectric Loss Tester 10kv Transformer Capacitance Tester

Introduction:

  • GDGS Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester is used to measure dissipation factor (PF) in heavy interference site such as power plants or power substations.
  • Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester can also be used in laboratory for  high accurate test. The set is whole in one designed: including precision digital bridge, power unit, reference capacitor (CN), step-up transformer and other electronic circuits. 
  • It's also using frequency shift technology, FFT (Fast Fourier Transform algorithm) and digital filtering. When started, it's running automatically and then outputs the results on LCD display and prints the results automatically.

 

Specifications:

No.

Item Name

Transformer Dielectric Loss Tester 10KV Transformer Capacitance Tester

1

Use conditions

-15ºC∽40ºC

RH<80%

2

Anti-interference

Frequency conversion

3

Power

AC 220V±10%

 

4

High output

0.5KV∽10KV

Every 0.1kV

Precision

2%

Maximum current  

200mA

Capacity

2000VA

5

Self-excited power

AC 0V∽50V/15A

45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

6

Resolving power

tgδ: 0.001%

Cx: 0.001pF

7

Precision

△tgδ:±(Reading*1.0%+0.040%)

△C x :±(Reading*1.0%+1.00PF)

8

measuring range

tgδ

Unlimited

C x

15pF < Cx < 300nF

 

10KV

Cx < 60  nF

 

 5KV

Cx < 150 nF

 

 1KV

Cx < 300 nF

CVT test

Cx < 300 nF

9

CVT range

10∽10000

accuracy

0.1%

Resolving power

0.01

10

Exterior dimension

350(L)×270(W)×270(H)

11

Memory size

The 200 group supports U disk data storage

12

Weight

28 Kg


Package List:

  • The GDGS Transformer Insulation Power Factor Tester;
  • User's manual and quality certification;
  • Test cable;
  •  Main lead;
  •  Additional color ribbon, paper roll and fuse;